Demonstrates FB_CylinderMonitor instances for all 4 sensor configurations
wired into the FB_WeldSequencer from the welding cell demo.
CYLINDERS IN THIS DEMO:
┌──────┬───────────────────────┬──────────────┬────────────────────────────┐
│ Inst │ Cylinder │ SensorConfig │ Notes │
├──────┼───────────────────────┼──────────────┼────────────────────────────┤
│ DB1 │ Clamp Cylinder │ ONE_FWD (1) │ Only clamp-closed sensor │
│ DB2 │ Weld Head │ TWO (3) │ Extended + retracted sensor │
│ DB3 │ Part Ejector │ ONE_BWD (2) │ Only retracted (home) sensor│
│ DB4 │ Gas Purge Valve │ NONE (0) │ No position sensor, timer │
└──────┴───────────────────────┴──────────────┴────────────────────────────┘
RESPONSE CONFIGURATION:
Timeout faults → PAUSE machine (operator can clear & resume)
Conflict faults → STOP machine (requires Reset before restart)
Lost position → STOP machine (requires Reset before restart)
CALL ORDER in OB (important — monitors must execute BEFORE sequencer):
1. FB_CylinderMonitor instances (DB1..DB4)
2. FB_CylFaultCollector (DB_CylFaults)
3. FB_WeldSequencer (DB_WeldSeq)
═══════════════════════════════════════════════════════════════════════════════*)
//─────────────────────────────────────────────────────────────────────────────
// INSTANCE DB DECLARATIONS (create these in TIA Portal project tree)
//
// DB_CylClamp : FB_CylinderMonitor
// DB_CylHead : FB_CylinderMonitor
// DB_CylEject : FB_CylinderMonitor
// DB_CylGas : FB_CylinderMonitor
// DB_CylFaults : FB_CylFaultCollector
// DB_WeldSeq : FB_WeldSequencer
//─────────────────────────────────────────────────────────────────────────────
//═════════════════════════════════════════════════════════════════════════════
// CYLINDER 1 — CLAMP (ONE_FWD: only clamp-closed sensor at FWD end)
// ─────────────────────────────────────────────────────────────────────────
// Physical setup:
// Proximity sensor mounted at closed (extended) jaw position ONLY.
// No sensor at open position — we assume open if no clamp command active.
//
// Error logic:
// Cmd_Fwd (clamp) active → Sen_Fwd (clamp closed) not confirmed in 2 s
// → FaultCode 1 (FWD timeout) → machine PAUSE
// Sen_Fwd unexpectedly active with no command? → Not detected (ONE_FWD limit)
//
// Advance in sequencer:
// Step 2 advance condition: DB_CylClamp.AtFwd
//═════════════════════════════════════════════════════════════════════════════
"DB_CylClamp"(
CylName := 'Clamp Cylinder',
SensorConfig := 1, // ONE_FWD
T_Timeout := T#2S, // 2 second fault timeout
Cmd_Fwd := "DB_WeldSeq".Act_Clamp, // Sequencer output drives FWD
Cmd_Bwd := NOT "DB_WeldSeq".Act_Clamp AND NOT "DB_WeldSeq".Seq_Faulted,
// Bwd inferred: not clamped & not faulted
Cmd_Reset := "PB_Reset",
Sen_Fwd := %I0.2, // Sen_ClampClosed hardware input
Sen_Bwd := FALSE, // No sensor at open position
Enable := "DB_WeldSeq".Seq_Running OR "DB_WeldSeq".Seq_Paused
);
//═════════════════════════════════════════════════════════════════════════════
// CYLINDER 2 — WELD HEAD (TWO sensors: extended + retracted)
// ─────────────────────────────────────────────────────────────────────────
// Physical setup:
// Sensor at fully extended (weld position) = Sen_Fwd → %I0.3
// Sensor at fully retracted (safe position) = Sen_Bwd → %I0.4
//
// Error logic:
// Extend cmd → Sen_Fwd not confirmed in 3 s → FaultCode 1 → PAUSE
// Retract cmd → Sen_Bwd not confirmed in 3 s → FaultCode 2 → PAUSE
// Both sensors TRUE simultaneously → FaultCode 3 → STOP
// Sensors both drop with no command active → FaultCode 4 (lost) → STOP
//
// Advance in sequencer:
// Step 3 advance: DB_CylHead.AtFwd
// Step 9 advance: DB_CylHead.AtBwd
//
// NOTE: Extend and Retract are separate solenoid outputs (bistable valve)
// CylCmd_FwdSafe → Act_HeadExtend solenoid
// CylCmd_BwdSafe → Act_HeadRetract solenoid
//═════════════════════════════════════════════════════════════════════════════
"DB_CylHead"(
CylName := 'Weld Head',
SensorConfig := 3, // TWO sensors
T_Timeout := T#3S, // 3 seconds (head travel takes longer)
Cmd_Fwd := "DB_WeldSeq".Act_HeadExtend,
Cmd_Bwd := "DB_WeldSeq".Act_HeadRetract,
Cmd_Reset := "PB_Reset",
Sen_Fwd := %I0.3, // Sen_HeadAtWeldPos
Sen_Bwd := %I0.4, // Sen_HeadRetracted
Enable := "DB_WeldSeq".Seq_Running OR "DB_WeldSeq".Seq_Paused
OR "DB_WeldSeq".Seq_Stopping
);
// ── Wire safe outputs back to physical DQs ───────────────────────────────
%Q0.1 := "DB_CylHead".CylCmd_FwdSafe; // Act_HeadExtend (gated)
%Q0.2 := "DB_CylHead".CylCmd_BwdSafe; // Act_HeadRetract (gated)
//═════════════════════════════════════════════════════════════════════════════
// CYLINDER 3 — PART EJECTOR (ONE_BWD: only home/retracted sensor)
// ─────────────────────────────────────────────────────────────────────────
// Physical setup:
// The ejector fires forward (extends) to push the part out.
// Sensor only at retracted (home) end — confirms ejector is clear/home.
// No sensor at extended (ejected) position.
//
// Error logic:
// Retract cmd (home return) → Sen_Bwd not confirmed in 1.5 s
// → FaultCode 2 (BWD timeout) → PAUSE
// Eject (FWD) cmd: no FWD sensor, so no timeout — just fires blind.
// After timer completes in sequencer, retract command issued.
//
// Advance in sequencer:
// Step 10 advance uses Sen_UnclampConf (%I0.7) which is separate.
// After cycle complete, this FB confirms ejector is home before next cycle.
//═════════════════════════════════════════════════════════════════════════════
"DB_CylEject"(
CylName := 'Part Ejector',
SensorConfig := 2, // ONE_BWD
T_Timeout := T#1500MS,
Cmd_Fwd := "DB_WeldSeq".Act_PartEject,
Cmd_Bwd := NOT "DB_WeldSeq".Act_PartEject
AND "DB_WeldSeq".Seq_Complete,
Cmd_Reset := "PB_Reset",
Sen_Fwd := FALSE, // No sensor at ejected position
Sen_Bwd := %I0.7, // Ejector home sensor (shared / Sen_UnclampConf area)
Enable := TRUE // Always enabled
);
//═════════════════════════════════════════════════════════════════════════════
// CYLINDER 4 — GAS PURGE VALVE (NONE: no position sensors)
// ─────────────────────────────────────────────────────────────────────────
// Physical setup:
// Simple solenoid valve — open or closed.
// No position feedback — valve assumed open when energised.
// No fault can be generated from position sensors (none exist).
//
// Error logic:
// NONE: the FB passes the command through, reports AT_FWD when commanded
// On/Off confirmed only by timer in the sequencer (Steps 4, 6, 8).
//
// NOTE: A pressure switch or flow sensor could be added here in future.
// Connect it to Sen_Fwd and change SensorConfig to ONE_FWD.
//═════════════════════════════════════════════════════════════════════════════
"DB_CylGas"(
CylName := 'Gas Purge Valve',
SensorConfig := 0, // NONE
T_Timeout := T#500MS, // Not used with NONE config (no timers start)
Cmd_Fwd := "DB_WeldSeq".Act_GasValve,
Cmd_Bwd := FALSE, // Single-acting valve — spring return
Cmd_Reset := "PB_Reset",
Sen_Fwd := FALSE,
Sen_Bwd := FALSE,
Enable := TRUE
);
//═════════════════════════════════════════════════════════════════════════════
// FAULT COLLECTOR — Aggregates all 4 cylinder faults
// Outputs feed directly into the sequencer Cmd_Pause / Cmd_Stop inputs
//═════════════════════════════════════════════════════════════════════════════
"DB_CylFaults"(
//── Fault bits ───────────────────────────────────────────────────────────
Cyl1_Fault := "DB_CylClamp".Fault_Active,
Cyl2_Fault := "DB_CylHead".Fault_Active,
Cyl3_Fault := "DB_CylEject".Fault_Active,
Cyl4_Fault := "DB_CylGas".Fault_Active,
Cyl5_Fault := FALSE,
Cyl6_Fault := FALSE,
Cyl7_Fault := FALSE,
Cyl8_Fault := FALSE,
//── Fault codes ───────────────────────────────────────────────────────────
Cyl1_FaultCode := "DB_CylClamp".FaultCode,
Cyl2_FaultCode := "DB_CylHead".FaultCode,
Cyl3_FaultCode := "DB_CylEject".FaultCode,
Cyl4_FaultCode := "DB_CylGas".FaultCode,
Cyl5_FaultCode := 0,
Cyl6_FaultCode := 0,
Cyl7_FaultCode := 0,
Cyl8_FaultCode := 0,
//── HMI fault texts ───────────────────────────────────────────────────────
Cyl1_FaultText := "DB_CylClamp".HMI_FaultText,
Cyl2_FaultText := "DB_CylHead".HMI_FaultText,
Cyl3_FaultText := "DB_CylEject".HMI_FaultText,
Cyl4_FaultText := "DB_CylGas".HMI_FaultText,
//── Machine response policy ───────────────────────────────────────────────
// Timeout → PAUSE (1): operator can check & reset, then resume
// Conflict → STOP (2): two sensors TRUE = hardware fault, needs investigation
// Lost pos → STOP (2): cylinder moved undetected = mechanical issue
Response_Timeout := 1,
Response_Conflict := 2,
Response_Lost := 2
);
//═════════════════════════════════════════════════════════════════════════════
// WELDING SEQUENCER — Wired with cylinder feedback and fault injection
//═════════════════════════════════════════════════════════════════════════════
"DB_WeldSeq"(
//── Mode & commands ─────────────────────────────────────────────────────
Mode_Auto := %I2.0,
Mode_Incr := %I2.1,
Cmd_Start := %I1.4,
Cmd_Reset := "PB_Reset",
// ── PAUSE: operator button OR cylinder fault requesting pause ──────────
Cmd_Pause := %I1.5
OR "DB_CylFaults".Cmd_MachinePause,
// ── STOP: operator button OR cylinder fault requesting stop ───────────
Cmd_Stop := %I1.6
OR "DB_CylFaults".Cmd_MachineStop,
Cmd_EStop := %I1.2,
Cmd_Incr := %I1.7,
Cmd_SkipStep := %I2.2,
StopCategory := %MW10,
//── Safety inputs ────────────────────────────────────────────────────────
Safety_DoorClosed := %I1.1,
Safety_EStopOK := %I1.0,
//── Sensors — using GATED outputs from cylinder monitors where possible ──
// Sequencer only sees "AtFwd/AtBwd" from healthy, confirmed cylinders.
// If cylinder monitor is faulted, AtFwd/AtBwd → FALSE → step never
// advances → watchdog trips → sequencer also faults. Belt & braces.
Sen_HomeFwd := %I0.0, // No cylinder monitor (robot)
Sen_HomeBwd := %I0.1,
// Step 2 clamp — uses cylinder monitor's AtFwd (confirmed clamp closed)
Sen_ClampClosed := "DB_CylClamp".AtFwd, // ← From monitor, not raw DI
// Steps 3 & 9 — weld head FWD/BWD (from monitor)
Sen_HeadAtWeldPos := "DB_CylHead".AtFwd, // ← Confirmed extended
Sen_HeadRetracted := "DB_CylHead".AtBwd, // ← Confirmed retracted
Sen_ArcDetect := %I0.5,
Sen_ArcOff := %I0.6,
// Step 10 unclamp (ejector home or unclamp sensor)
Sen_UnclampConf := "DB_CylEject".AtBwd, // ← Ejector home confirmed
//── Actuator outputs ─────────────────────────────────────────────────────
// NOTE: Act_HeadExtend and Act_HeadRetract go through the head cylinder
// monitor's gated outputs (see %Q assignments above).
// Act_Clamp goes direct here — the monitor checks it on its own scan.
Act_Clamp => %Q0.0,
Act_HeadExtend => "DB_CylHead_CmdFwd_Raw", // Internal tag; monitor gates it to %Q0.1
Act_HeadRetract => "DB_CylHead_CmdBwd_Raw", // Internal tag; monitor gates it to %Q0.2
Act_GasValve => %Q0.3,
Act_WeldEnable => %Q0.4,
Act_Unclamp => %Q0.5,
Act_PartEject => %Q0.6,
//── Status outputs ───────────────────────────────────────────────────────
Seq_Running => %Q1.0,
Seq_Paused => %Q1.1,
Seq_Faulted => %Q1.2,
Seq_Complete => %Q1.3,
ActiveStep => %MW20,
SeqState => %MW22,
FaultCode => %MW24,
StepAdvanceReady => %M5.0,
IncrWaiting => %M5.1,
CycleCount => %MD30
);
//═════════════════════════════════════════════════════════════════════════════
// HMI WIRING SUMMARY
// Wire these tags to your WinCC/Comfort panel for operator guidance:
//
// TAG SOURCE HMI ELEMENT
// ─────────────────────────────────────────────────────────────────────────
// DB_WeldSeq.ActiveStep → %MW20 Step indicator (1-10)
// DB_WeldSeq.SeqState → %MW22 State text list
// DB_WeldSeq.FaultCode → %MW24 Sequencer alarm
// DB_CylFaults.FirstFaultText First fault banner text
// DB_CylFaults.CylFaultWord Cylinder fault bitmask (overview)
// DB_CylFaults.ActiveFaultCount Number of active faults
// DB_CylClamp.CylState Clamp position indicator
// DB_CylClamp.HMI_StatusText Clamp status string
// DB_CylHead.CylState Head position indicator
// DB_CylHead.HMI_StatusText Head status string
// DB_CylEject.CylState Ejector status
// DB_CylHead.Moving Moving animation trigger
// DB_CylFaults.Cmd_Warning → %Q1.4 Amber warning lamp
// DB_WeldSeq.Seq_Faulted → %Q1.2 Red fault lamp
// DB_WeldSeq.IncrWaiting → %M5.1 "Press INCR" flashing indicator
//═════════════════════════════════════════════════════════════════════════════