FC_GetSetLocalTime
Version: 1.1
Language: SCL (Structured Control Language) — Siemens TIA Portal
Return Type: Int
Overview
FC_GetSetLocalTime is a reusable function block for Siemens PLCs that provides a unified interface to read the current local time or write (set) a new local date and time. It wraps the TIA Portal system instructions RD_LOC_T and WR_LOC_T into a single, easy-to-call function.
Parameters
Inputs
| Parameter | Type | Description |
|---|---|---|
xWrite |
BOOL |
FALSE = Read current local time. TRUE = Write a new local time. |
dtLocal |
DTL |
When writing: pass the desired new date/time here. When reading: this parameter receives the current date/time as output. |
Note:
dtLocalacts as both an input and output depending on the mode selected byxWrite.
Outputs
| Parameter | Type | Description |
|---|---|---|
xDone |
BOOL |
Set to TRUE when the operation completes without error. |
xError |
BOOL |
Set to TRUE when the operation fails. |
wStatus |
WORD |
Detailed status or error code returned by the system instruction (e.g., 16#0000 = no error). |
Return Value
| Value | Meaning |
|---|---|
0 |
Operation successful (OK) |
> 0 |
Warning |
< 0 |
Error |
How It Works
The function uses a simple IF/ELSE branch controlled by the xWrite flag:
xWrite = FALSE → Calls RD_LOC_T → Reads current local time into dtLocal
xWrite = TRUE → Calls WR_LOC_T → Writes dtLocal value as new local time
In both cases:
- If the system instruction returns
ret = 0,xDoneis set toTRUE. - If
ret ≠ 0,xErroris set toTRUEandwStatusholds the error code for diagnostics. - The function itself returns
retas its integer return value.
Usage Examples
Read Current Local Time
RET_VAL := FC_GetSetLocalTime(
xWrite := FALSE,
dtLocal => CurrentTime // CurrentTime will be filled with the current date/time
);
Write / Set a New Local Time
RET_VAL := FC_GetSetLocalTime(
xWrite := TRUE,
dtLocal := NewTime // NewTime contains the desired date/time to set
);
Error Handling
After calling the function, always check the outputs before proceeding:
IF xDone THEN
// Operation was successful
ELSIF xError THEN
// Handle error — inspect wStatus for the specific error code
END_IF;
The wStatus word follows standard Siemens status code conventions. A value of 16#0000 indicates no error.
Dependencies
This function relies on the following Siemens TIA Portal system instructions:
| Instruction | Purpose |
|---|---|
RD_LOC_T |
Reads the current local date and time into a DTL variable |
WR_LOC_T |
Writes a new local date and time from a DTL variable |
Both instructions are available on S7-1200 and S7-1500 series PLCs.
Data Type Reference — DTL
DTL (Date and Time Long) is a Siemens-specific data type that stores date and time with nanosecond precision.
| Field | Type | Description |
|---|---|---|
YEAR |
UINT |
Year (e.g., 2024) |
MONTH |
USINT |
Month (1–12) |
DAY |
USINT |
Day (1–31) |
WEEKDAY |
USINT |
Day of week (1=Sunday … 7=Saturday) |
HOUR |
USINT |
Hour (0–23) |
MINUTE |
USINT |
Minute (0–59) |
SECOND |
USINT |
Second (0–59) |
NANOSECOND |
UDINT |
Nanoseconds (0–999,999,999) |
Notes
- The function resets
xDone,xError, andwStatusat the start of every call, so outputs always reflect the most recent execution. - Only one operation (read or write) is performed per function call.
- This function does not handle time zone conversion — it works with the local time as configured on the PLC.