# FB_CylinderMonitor — S7-1500 SCL Universal Cylinder Supervisor
> **Platform:** Siemens S7-1500 | TIA Portal V18+ | SCL
> **Blocks:** `FB_CylinderMonitor` · `FB_CylFaultCollector`
> **Companion to:** [`FB_WeldSequencer`](../README.md)
A drop-in cylinder monitoring library for any pneumatic or hydraulic actuator. Handles all real-world sensor configurations — zero, one, or two position sensors — generates direction-aware timeout faults, detects sensor conflicts and lost positions, gates actuator outputs for safety, and feeds structured fault data directly to an HMI and machine sequencer.
---
## Table of Contents
1. [Why This Exists](#1-why-this-exists)
2. [Files](#2-files)
3. [Sensor Configuration Options](#3-sensor-configuration-options)
4. [Fault Logic Per Configuration](#4-fault-logic-per-configuration)
5. [FB_CylinderMonitor — Interface](#5-fb_cylindermonitor--interface)
6. [FB_CylFaultCollector — Interface](#6-fb_cylfaultcollector--interface)
7. [Output Gating Pattern](#7-output-gating-pattern)
8. [Integration with FB_WeldSequencer](#8-integration-with-fb_weldsequencer)
9. [Demo: Welding Cell (4 cylinders)](#9-demo-welding-cell-4-cylinders)
10. [HMI Integration](#10-hmi-integration)
11. [TIA Portal Setup](#11-tia-portal-setup)
12. [Timing Reference](#12-timing-reference)
13. [Fault Code Reference](#13-fault-code-reference)
14. [Adapting for Other Applications](#14-adapting-for-other-applications)
15. [Safety Notes](#15-safety-notes)
---
## 1. Why This Exists
Every cylinder in a machine needs the same boilerplate logic:
- Did it reach position in time? If not → fault
- Are both sensors TRUE at once? That's wiring or hardware failure → fault
- Did it leave position without being commanded? → fault
- What should the machine do when it faults — pause or stop?
- What should the operator see on the HMI?
Writing this 20+ times per machine is error-prone and inconsistent. `FB_CylinderMonitor` encapsulates it once, handles all sensor topologies, and gives you clean `AtFwd`/`AtBwd` booleans that replace raw sensor reads in your step advance conditions.
---
## 2. Files
```
📁 CylinderMonitor/
├── FB_CylinderMonitor.scl # FB_CylinderMonitor + FB_CylFaultCollector
├── DEMO_WeldCellIntegration.scl # Integration demo (4 cylinders + sequencer)
└── README_CylinderMonitor.md # This file
```
---
## 3. Sensor Configuration Options
Set `SensorConfig` (INT) on each FB instance:
| Value | Constant | Sensor Setup | Typical Use |
|---|---|---|---|
| `0` | `CFG_NONE` | No sensors | Valves, no-feedback actuators |
| `1` | `CFG_ONE_FWD` | Sensor at FWD (extended) end only | Clamps, grippers — only care about "closed" |
| `2` | `CFG_ONE_BWD` | Sensor at BWD (retracted) end only | Ejectors — only care about "home" |
| `3` | `CFG_TWO` | Sensor at both ends | Weld heads, positioners, gates |
### Which configuration to use?
```
Q: Does the cylinder need to confirm both extended AND retracted?
YES → CFG_TWO (3)
Q: Only need to know it's closed/extended?
YES → CFG_ONE_FWD (1)
Q: Only need to know it's home/retracted?
YES → CFG_ONE_BWD (2)
Q: No sensor at all (timer-only advance)?
YES → CFG_NONE (0)
```
---
## 4. Fault Logic Per Configuration
### CFG_NONE (0) — No faults possible from position
```
Cmd_Fwd ON ──────────────────────────────────▶ CylCmd_FwdSafe ON
CylState = AT_FWD (trusted)
No sensors → no timeout → no conflict
Advance logic: use sequencer's step timer
```
### CFG_ONE_FWD (1) — Fault on FWD only
```
Cmd_Fwd ON ──┬──────────────────────▶ CylCmd_FwdSafe ON
│ Sen_Fwd? ──TRUE────▶ AtFwd = TRUE ✓ (timer reset)
│ └─FALSE───▶ T_Timeout running
│ │
│ ▼ T_Timeout elapsed
│ FaultCode = 1 (FWD TIMEOUT)
│ Fault_Active = TRUE
│ CylCmd_FwdSafe → FALSE (gated off)
Cmd_Bwd ON ──▶ No BWD timeout possible (no BWD sensor)
CylState reports AT_BWD when FWD sensor clears
```
### CFG_ONE_BWD (2) — Fault on BWD only
```
Cmd_Bwd ON ──┬──────────────────────▶ CylCmd_BwdSafe ON
│ Sen_Bwd? ──TRUE────▶ AtBwd = TRUE ✓ (timer reset)
│ └─FALSE───▶ T_Timeout running
│ ▼ T_Timeout elapsed
│ FaultCode = 2 (BWD TIMEOUT)
Cmd_Fwd ON ──▶ No FWD timeout (no FWD sensor)
CylState reports AT_FWD when BWD sensor clears
```
### CFG_TWO (3) — Full fault coverage
```
Cmd_Fwd ON ──▶ Sen_Fwd? ─TRUE──▶ AtFwd ✓ timer cancelled
└─FALSE─▶ Timeout FWD → FaultCode 1
Cmd_Bwd ON ──▶ Sen_Bwd? ─TRUE──▶ AtBwd ✓ timer cancelled
└─FALSE─▶ Timeout BWD → FaultCode 2
BOTH sensors TRUE simultaneously → FaultCode 3 (CONFLICT) → immediate fault
No cmd + was at known pos + both sensors go FALSE → FaultCode 4 (LOST)
Both Cmd_Fwd AND Cmd_Bwd TRUE → FaultCode 3 (command conflict)
```
---
## 5. FB_CylinderMonitor — Interface
### VAR_INPUT
| Name | Type | Description |
|---|---|---|
| `CylName` | `String[32]` | Human name, e.g. `'Clamp Cylinder'` — used in HMI text |
| `SensorConfig` | `Int` | 0=NONE, 1=ONE_FWD, 2=ONE_BWD, 3=TWO |
| `T_Timeout` | `Time` | Max time for cylinder to reach position |
| `Cmd_Fwd` | `Bool` | Extend / close command |
| `Cmd_Bwd` | `Bool` | Retract / open command |
| `Cmd_Reset` | `Bool` | Rising edge clears fault |
| `Sen_Fwd` | `Bool` | Forward / extended position sensor |
| `Sen_Bwd` | `Bool` | Backward / retracted position sensor |
| `Enable` | `Bool` | FALSE = ignore commands, hold state |
### VAR_OUTPUT
| Name | Type | Description |
|---|---|---|
| `CylCmd_FwdSafe` | `Bool` | **Gated FWD output** — connect to DQ |
| `CylCmd_BwdSafe` | `Bool` | **Gated BWD output** — connect to DQ |
| `AtFwd` | `Bool` | Position confirmed at FWD |
| `AtBwd` | `Bool` | Position confirmed at BWD |
| `Intermediate` | `Bool` | Between positions (TWO config, no cmd) |
| `Moving` | `Bool` | Command active, not yet confirmed |
| `Fault_Active` | `Bool` | Any fault present |
| `Fault_FwdTimeout` | `Bool` | Specific fault bit |
| `Fault_BwdTimeout` | `Bool` | Specific fault bit |
| `Fault_Conflict` | `Bool` | Sensor conflict fault bit |
| `Fault_Lost` | `Bool` | Lost position fault bit |
| `FaultCode` | `Int` | Numeric code (04) |
| `CylState` | `Int` | State code (06) |
| `HMI_StatusText` | `String[80]` | Ready-to-display status |
| `HMI_FaultText` | `String[80]` | Ready-to-display fault message |
---
## 6. FB_CylFaultCollector — Interface
Aggregates up to 8 cylinder monitor faults into one summary. Wire its outputs to the sequencer's `Cmd_Pause` and `Cmd_Stop`.
### Key Outputs
| Name | Type | Description |
|---|---|---|
| `CylFaultAny` | `Bool` | OR of all cylinder faults |
| `CylFaultWord` | `Word` | Bitmask — bit 0 = Cyl1, bit 7 = Cyl8 |
| `Cmd_MachinePause` | `Bool` | **Wire to sequencer `Cmd_Pause`** |
| `Cmd_MachineStop` | `Bool` | **Wire to sequencer `Cmd_Stop`** |
| `Cmd_Warning` | `Bool` | Amber lamp — non-stopping fault |
| `FirstFaultText` | `String[80]` | First fault message for HMI banner |
| `ActiveFaultCount` | `Int` | Number of cylinders currently faulted |
### Machine Response Configuration
| Input | Value | Effect |
|---|---|---|
| `Response_Timeout` | `0` | Warning only — machine keeps running |
| `Response_Timeout` | `1` | Pause machine |
| `Response_Timeout` | `2` | Stop machine (requires Reset) |
| `Response_Conflict` | `0/1/2` | Same options |
| `Response_Lost` | `0/1/2` | Same options |
**Recommended defaults:**
```scl
Response_Timeout := 1; // Pause — timeout may be temporary, operator can check
Response_Conflict := 2; // Stop — two sensors both TRUE = hardware fault
Response_Lost := 2; // Stop — cylinder moved without command = mechanical issue
```
---
## 7. Output Gating Pattern
The core safety pattern of this FB is **output gating**. Instead of writing:
```scl
// ❌ Unsafe — raw command goes direct to DQ
%Q0.1 := Act_HeadExtend;
```
You write:
```scl
// ✅ Safe — passes through monitor, gated off on fault
"DB_CylHead"(
Cmd_Fwd := Act_HeadExtend,
...
);
%Q0.1 := "DB_CylHead".CylCmd_FwdSafe; // Only energises if healthy
```
When a fault occurs (timeout, conflict, lost position):
1. `CylCmd_FwdSafe``FALSE` immediately (same scan as fault detection)
2. Solenoid valve de-energised → cylinder stops
3. `Fault_Active``TRUE` → collector → sequencer `Cmd_Pause` or `Cmd_Stop`
4. `HMI_FaultText` → operator message describes exactly what failed
---
## 8. Integration with FB_WeldSequencer
The two FBs communicate in both directions:
```
FB_CylinderMonitor FB_WeldSequencer
──────────────────── ─────────────────────────────
AtFwd ─────────────────────────────▶ Sen_ClampClosed (step 2 advance)
AtFwd ─────────────────────────────▶ Sen_HeadAtWeldPos (step 3 advance)
AtBwd ─────────────────────────────▶ Sen_HeadRetracted (step 9 advance)
Fault_Active
└──▶ FB_CylFaultCollector
Cmd_MachinePause ──────────▶ Cmd_Pause (OR with operator PB)
Cmd_MachineStop ──────────▶ Cmd_Stop (OR with operator PB)
FB_WeldSequencer FB_CylinderMonitor
───────────────────────────── ────────────────────
Act_HeadExtend ─────────────────────▶ Cmd_Fwd
Act_HeadRetract ────────────────────▶ Cmd_Bwd
Seq_Running OR Seq_Paused ──────────▶ Enable
```
### Step Advance with Monitor vs Raw Sensor
| Without Monitor | With Monitor |
|---|---|
| `_stepAdvReady := Sen_ClampClosed` | `_stepAdvReady := "DB_CylClamp".AtFwd` |
| Advances even if clamp timed out | Will not advance if monitor is faulted |
| No timeout detection | FaultCode 1 triggers machine pause |
Using `AtFwd`/`AtBwd` from the monitor instead of raw sensor inputs means a faulted cylinder **also prevents step advance**, so the sequencer's own watchdog timer provides a belt-and-braces fallback catch.
---
## 9. Demo: Welding Cell (4 Cylinders)
The demo file `DEMO_WeldCellIntegration.scl` shows all four configurations side by side:
| Instance | Cylinder | Config | Timeout | Fault Response |
|---|---|---|---|---|
| `DB_CylClamp` | Clamp | ONE_FWD | 2 s | Pause |
| `DB_CylHead` | Weld Head | TWO | 3 s | Pause (timeout) / Stop (conflict) |
| `DB_CylEject` | Part Ejector | ONE_BWD | 1.5 s | Pause |
| `DB_CylGas` | Gas Valve | NONE | n/a | n/a |
### Execution Order (critical)
In your OB (OB1 or OB30), call in this order:
```
1st → "DB_CylClamp"(...) FB_CylinderMonitor
2nd → "DB_CylHead"(...) FB_CylinderMonitor
3rd → "DB_CylEject"(...) FB_CylinderMonitor
4th → "DB_CylGas"(...) FB_CylinderMonitor
5th → "DB_CylFaults"(...) FB_CylFaultCollector
6th → "DB_WeldSeq"(...) FB_WeldSequencer
```
Monitors run first so that `AtFwd`/`AtBwd` and `Fault_Active` values are fresh when the sequencer evaluates step advance conditions and Cmd_Pause/Stop in the same scan.
---
## 10. HMI Integration
### Recommended Screen Objects
#### Cylinder Overview Faceplate (one per cylinder)
| Element | Tag | Type |
|---|---|---|
| Status text | `DB_CylClamp.HMI_StatusText` | Text field |
| Fault text | `DB_CylClamp.HMI_FaultText` | Text field (red, visible on fault) |
| State indicator | `DB_CylClamp.CylState` | Bar/value with colour map |
| Moving animation | `DB_CylClamp.Moving` | Animated cylinder graphic |
| At FWD lamp | `DB_CylClamp.AtFwd` | Green indicator |
| At BWD lamp | `DB_CylClamp.AtBwd` | Green indicator |
| Fault lamp | `DB_CylClamp.Fault_Active` | Red indicator |
#### CylState Colour Map (for bargraph or rectangle)
| Value | Colour | Label |
|---|---|---|
| 0 | Grey | Idle |
| 1 | Yellow | Moving FWD |
| 2 | Green | At FWD ✓ |
| 3 | Yellow | Moving BWD |
| 4 | Green | At BWD ✓ |
| 5 | Orange | Intermediate |
| 6 | Red | FAULTED |
#### Global Alarm Banner
```
Tag: DB_CylFaults.FirstFaultText
Visible: DB_CylFaults.CylFaultAny = TRUE
Background: Red
Example text: "Weld Head: FWD TIMEOUT — check cylinder, solenoid and FWD sensor"
```
#### Fault Bitmask Display (overview bar)
```
Tag: DB_CylFaults.CylFaultWord (WORD)
Display as: 8 individual bit lamps
Bit 0 = Clamp Bit 1 = Head Bit 2 = Ejector Bit 3 = Gas ...
```
#### Operator Guidance Text Logic
For each cylinder fault, the HMI_FaultText already tells the operator exactly what to check:
```
FaultCode 1 → "Clamp Cylinder: FWD TIMEOUT — check cylinder, solenoid and FWD sensor"
FaultCode 2 → "Weld Head: BWD TIMEOUT — check cylinder, solenoid and BWD sensor"
FaultCode 3 → "Weld Head: SENSOR CONFLICT — FWD + BWD both active. Check wiring/sensors"
FaultCode 4 → "Weld Head: LOST POSITION — cylinder moved without command. Check mechanics"
```
No lookup table needed — the text is generated inside the FB using the `CylName` you configured.
---
## 11. TIA Portal Setup
### Create Instance DBs
For each cylinder, right-click project tree → **Add new block****Data Block** → Instance DB of `FB_CylinderMonitor`:
```
DB_CylClamp : FB_CylinderMonitor
DB_CylHead : FB_CylinderMonitor
DB_CylEject : FB_CylinderMonitor
DB_CylGas : FB_CylinderMonitor
DB_CylFaults : FB_CylFaultCollector
```
### Initial Parameter Setup (in startup OB or first-scan block)
```scl
// Set cylinder names and configs once at startup
// (or set directly in instance DB initial values in TIA Portal)
"DB_CylClamp".CylName := 'Clamp Cylinder';
"DB_CylClamp".SensorConfig := 1;
"DB_CylClamp".T_Timeout := T#2S;
"DB_CylHead".CylName := 'Weld Head';
"DB_CylHead".SensorConfig := 3;
"DB_CylHead".T_Timeout := T#3S;
"DB_CylEject".CylName := 'Part Ejector';
"DB_CylEject".SensorConfig := 2;
"DB_CylEject".T_Timeout := T#1500MS;
"DB_CylGas".CylName := 'Gas Purge Valve';
"DB_CylGas".SensorConfig := 0;
```
Alternatively, set initial values directly in the instance DB's data view in TIA Portal — these persist through power cycles.
---
## 12. Timing Reference
| Cylinder Type | Recommended T_Timeout | Notes |
|---|---|---|
| Fast pneumatic (< 50 mm) | `T#1S` | Small bore, short stroke |
| Standard pneumatic | `T#2S` | Most clamps, grippers |
| Long-stroke pneumatic | `T#3S``T#5S` | Weld heads, gates |
| Hydraulic | `T#5S``T#15S` | Slower by nature |
| Spring-return valve | N/A (NONE config) | No position sensor |
**Rule of thumb:** Set timeout to 3× the expected travel time. Fast enough to catch real faults, slow enough to avoid nuisance trips on normal variation.
---
## 13. Fault Code Reference
| Code | Name | Cause | HMI Message | Machine Action |
|---|---|---|---|---|
| `0` | No fault | Normal | *(empty)* | None |
| `1` | FWD timeout | Sen_Fwd not TRUE within T_Timeout after Cmd_Fwd | `"[Name]: FWD TIMEOUT — check cylinder, solenoid and FWD sensor"` | Pause (configurable) |
| `2` | BWD timeout | Sen_Bwd not TRUE within T_Timeout after Cmd_Bwd | `"[Name]: BWD TIMEOUT — check cylinder, solenoid and BWD sensor"` | Pause (configurable) |
| `3` | Conflict | Sen_Fwd AND Sen_Bwd both TRUE, or Cmd_Fwd AND Cmd_Bwd both TRUE | `"[Name]: SENSOR CONFLICT — FWD + BWD both active. Check wiring/sensors"` | Stop (configurable) |
| `4` | Lost position | Was at known position; both sensors dropped with no command | `"[Name]: LOST POSITION — cylinder moved without command. Check mechanics"` | Stop (configurable) |
---
## 14. Adapting for Other Applications
### Add a pressure/flow sensor as virtual FWD confirmation
```scl
// Gas valve with pressure feedback
"DB_CylGas"(
CylName := 'Gas Valve',
SensorConfig := 1, // ONE_FWD
T_Timeout := T#1S,
Cmd_Fwd := Act_GasValve,
Sen_Fwd := PressureSwitch_OK, // Add this DI
...
);
```
### Motor or servo (use as virtual "cylinder" with limit switches)
```scl
"DB_CylSlide"(
CylName := 'Transfer Slide',
SensorConfig := 3,
T_Timeout := T#4S,
Cmd_Fwd := SlideMotor_Fwd,
Cmd_Bwd := SlideMotor_Rev,
Sen_Fwd := LS_SlideForward,
Sen_Bwd := LS_SlideReverse,
...
);
```
### Changing timeout at runtime
```scl
// Speed-dependent timeout (slow mode vs normal mode)
IF SlowMode THEN
"DB_CylHead".T_Timeout := T#8S;
ELSE
"DB_CylHead".T_Timeout := T#3S;
END_IF;
```
Note: `T_Timeout` is read by the TON each scan changes take effect immediately on the next timer start.
### More than 8 cylinders
Extend `FB_CylFaultCollector` array declarations from `[1..8]` to `[1..N]` and add corresponding `VAR_INPUT` slots.
---
## 15. Safety Notes
> ⚠️ `FB_CylinderMonitor` is a **diagnostic and convenience layer**. It is NOT a safety function and should NOT be used as the sole means of protecting personnel from cylinder movement.
### This FB provides (diagnostic/operational layer):
- Timeout detection pause or stop production
- Sensor conflict immediate output gate + machine stop
- HMI guidance text for operator troubleshooting
- Output gating (software level only not certified)
### This FB does NOT replace (safety layer):
- **Hardware safety valves** (5/2 safety valve with spring return for E-Stop)
- **Dual-channel safety relay** monitoring for guard interlocks
- **Safety PLC** (S7-1500F) for PLd/SIL2 applications
- **Mechanical hard stops** preventing overtravel
- **Pressure relief valves** on hydraulic systems
### Minimum safety architecture:
```
E-Stop ──▶ Safety Relay ──▶ Safety Valve ──▶ Cylinder (power removed in hardware)
└──▶ Safety_EStopOK input on FB_WeldSequencer (software layer)
Door open ──▶ Safety Switch ──▶ Safety Relay
└──▶ Safety_DoorClosed input on FB_WeldSequencer
```
The cylinder monitor's `CylCmd_FwdSafe` / `CylCmd_BwdSafe` outputs control directional valves only. Power removal for E-Stop must be done at the hardware safety relay level, not by this FB.
---
## Changelog
| Version | Date | Notes |
|---|---|---|
| 0.1 | 2025 | Initial release 4 sensor config types, 4 fault codes, HMI text |
---
## Licence
MIT free to use and adapt.
---
*For the full welding cell sequencer (10 steps, AUTO/INCR mode, stop categories), see [`README.md`](../README.md).*