S7-1500 SCL Sequencer — Advanced 10-Step Welding Cell
Platform: Siemens S7-1500 | TIA Portal V18+ | SCL (Structured Control Language) Block:
FB_WeldSequencer| Optimized Access | IEC 61131-3 compliant
A production-ready, feature-complete 10-step sequencer for a MIG/MAG robotic welding cell demonstrating all advanced sequencer patterns: AUTO/INCREMENT modes, PAUSE vs STOP, IEC Stop Categories (CAT0/CAT1/CAT2), Step Skip, Step Disable, Safety-Locked Steps, sensor-based advance, dual-sensor (FWD/BWD) advance, and pure timer advance.
Table of Contents
- Feature Overview
- File Structure
- I/O Map
- Sequencer Modes
- State Machine
- Stop Categories (IEC 60204-1)
- Pause vs Stop
- Step-by-Step Breakdown
- Step Advance Types
- Skip / Disable / Safety-Lock
- Fault Codes
- HMI Integration
- TIA Portal Setup
- Adapting the Code
- Safety Notes
1. Feature Overview
| Feature | Description |
|---|---|
| AUTO mode | Steps advance immediately when advance condition is met |
| INCREMENT mode | Condition must be TRUE then operator presses Cmd_Incr to advance |
| PAUSE | Soft hold — all outputs frozen in place; resume resumes same step |
| STOP (CAT2) | Hard hold — requires Cmd_Reset to return to IDLE |
| E-Stop CAT0 | Immediate: all outputs de-energised in the same scan |
| E-Stop CAT1 | Controlled: current step finishes its "safe motion" then stops |
| E-Stop CAT2 | Suspend: outputs frozen until reset (same as STOP) |
| Skip Step | Operator can force-advance any step NOT safety-locked |
| Disable Step | Individual steps can be permanently skipped (e.g. bypass unused stations) |
| Safety-Locked Steps | Steps 1, 5, 7 cannot be skipped — operator SkipStep is silently ignored |
| Timer Advance | Steps 4, 6, 8 advance on IEC timer expiry (no sensor needed) |
| 1-Sensor Advance | Steps 2, 5, 7, 10 advance on single sensor |
| 2-Sensor Advance | Steps 1, 3, 9 use FWD + BWD sensors with conflict detection |
| Step Watchdog | 30 s watchdog per step — faults if a step takes too long |
| Cycle Counter | Persistent CycleCount DINT increments on every completed cycle |
2. File Structure
📁 WeldSequencer/
├── FB_WeldSequencer.scl # Main Function Block — all sequencer logic
└── README.md # This file
Note: In TIA Portal, create one Instance DB for the FB (e.g.
DB_WeldSeq). The instance DB holds all internal state, timers, and configuration arrays.
3. I/O Map
Digital Inputs (DI)
| Address | Tag Name | Description | Used in Step(s) |
|---|---|---|---|
%I0.0 |
Sen_HomeFwd |
Fixture at home position | 1 |
%I0.1 |
Sen_HomeBwd |
Fixture NOT in work zone (redundant) | 1 |
%I0.2 |
Sen_ClampClosed |
Clamp jaw fully closed | 2 |
%I0.3 |
Sen_HeadAtWeldPos |
Weld head fully EXTENDED | 3, 9 |
%I0.4 |
Sen_HeadRetracted |
Weld head fully RETRACTED | 3, 9 |
%I0.5 |
Sen_ArcDetect |
Arc current detected (welder feedback) | 5 |
%I0.6 |
Sen_ArcOff |
Arc extinguished (current < threshold) | 7 |
%I0.7 |
Sen_UnclampConf |
Clamp open / part ejected | 10 |
%I1.0 |
Safety_EStopOK |
Safety relay: TRUE = E-Stop clear | All |
%I1.1 |
Safety_DoorClosed |
Safety gate NC contact | All |
%I1.2 |
Cmd_EStop |
E-Stop command (from safety relay or HMI) | All |
%I1.3 |
Cmd_Reset |
Reset faults / return to IDLE | All |
%I1.4 |
Cmd_Start |
Start cycle / Resume after pause | All |
%I1.5 |
Cmd_Pause |
Pause at current step | All |
%I1.6 |
Cmd_Stop |
CAT2 Stop | All |
%I1.7 |
Cmd_Incr |
Increment step (INCREMENT mode only) | All |
%I2.0 |
Mode_Auto |
Automatic mode selector | All |
%I2.1 |
Mode_Incr |
Increment mode selector | All |
%I2.2 |
Cmd_SkipStep |
Skip current step (if not locked) | All |
Digital Outputs (DQ)
| Address | Tag Name | Description | Active in Step(s) |
|---|---|---|---|
%Q0.0 |
Act_Clamp |
Clamp solenoid | 2 → 9 |
%Q0.1 |
Act_HeadExtend |
Weld head extend solenoid | 3 → 8 |
%Q0.2 |
Act_HeadRetract |
Weld head retract solenoid | 9 |
%Q0.3 |
Act_GasValve |
Shielding gas solenoid valve | 4 → 8 |
%Q0.4 |
Act_WeldEnable |
Welder power enable relay | 5, 6 |
%Q0.5 |
Act_Unclamp |
Unclamp solenoid | 10 |
%Q0.6 |
Act_PartEject |
Part ejector cylinder solenoid | 10 |
%Q1.0 |
Seq_Running |
Sequence running indicator | — |
%Q1.1 |
Seq_Paused |
Sequence paused indicator | — |
%Q1.2 |
Seq_Faulted |
Fault active indicator | — |
%Q1.3 |
Seq_Complete |
Cycle complete indicator | — |
Memory / HMI Words
| Address | Tag Name | Type | Description |
|---|---|---|---|
%MW10 |
StopCategory |
INT | E-Stop category: 0, 1, or 2 |
%MW20 |
ActiveStep |
INT | Currently executing step |
%MW22 |
SeqState |
INT | State machine code (0–6) |
%MW24 |
FaultCode |
INT | Active fault code |
%M5.0 |
StepAdvanceReady |
BOOL | Advance condition satisfied |
%M5.1 |
IncrWaiting |
BOOL | Waiting for Incr in INCREMENT mode |
%MD30 |
CycleCount |
DINT | Completed cycles |
4. Sequencer Modes
AUTO Mode (Mode_Auto = TRUE)
Cmd_Start ──→ Step 1 ──[cond met]──→ Step 2 ──[cond met]──→ ... ──→ Step 10 ──→ COMPLETE
The sequence runs end-to-end without any operator input once started. Each step advances the instant its advance condition becomes TRUE. Intended for normal production operation.
INCREMENT Mode (Mode_Incr = TRUE)
Cmd_Start ──→ Step 1 ──[cond met + Cmd_Incr]──→ Step 2 ──[cond met + Cmd_Incr]──→ ...
The sequencer waits at each step until:
- The step's advance condition is
TRUE(sensor or timer) - AND the operator presses
Cmd_Incr
The IncrWaiting output goes TRUE when condition is met but waiting for the increment button — useful for an HMI indicator ("Ready to advance — press INCR").
Use cases: First article inspection, commissioning, slow-speed prove-out, fault recovery.
Mode switching: Change modes between cycles only (while in IDLE or COMPLETE). Switching mid-cycle is accepted by the FB but may cause unexpected step dwell.
5. State Machine
┌─────────────────────────────────────────────────────┐
│ │
▼ │
┌─────────────────┐ Cmd_Start + safe ┌───────────────────┐ │
│ 0 — IDLE │ ─────────────────────▶ │ 1 — RUNNING │ │
└─────────────────┘ └───────────────────┘ │
▲ │ │ │ │ │
│ Cmd_Reset Cmd_Pause│ │ │ │last step
│ (from STOPPED/FAULTED/ ◀────────┘ │ │ ▼
│ COMPLETE) ┌──────────────┐ │ │ ┌──────────────┐
│ │ 2 — PAUSED │ │ │ │ 6 — COMPLETE │─┘
│ └──────────────┘ │ │ └──────────────┘
│ Cmd_Stop▼ │ │
│ ┌──────────────┐ │ E-Stop
│ │ 4 — STOPPED │◀───┘ CAT1│
│ └──────────────┘ ▼
│ ┌─────────────────────┐
│ │ 3 — STOPPING_CAT1 │
│ └─────────────────────┘
│ ┌──────────────┐ │ step done or timeout
│ ◀────────────────── │ 5 — FAULTED │◀─────────┘
│ Cmd_Reset └──────────────┘
│ + E-Stop clear ▲
│ + door closed │ E-Stop CAT0 / door open
└───────────────────────────────────────┘
| State | Code | Outputs | Resume? | Reset? |
|---|---|---|---|---|
| IDLE | 0 | Weld/gas/motion off | — | — |
| RUNNING | 1 | Per active step | — | — |
| PAUSED | 2 | Held (frozen) | Cmd_Start |
— |
| STOPPING_CAT1 | 3 | Current step active | — | After → STOPPED |
| STOPPED | 4 | Safe state | — | Cmd_Reset |
| FAULTED | 5 | ALL off | — | Cmd_Reset + clear |
| COMPLETE | 6 | Weld/gas off | Cmd_Start (new cycle) |
Cmd_Reset |
6. Stop Categories (IEC 60204-1)
Set StopCategory (INT) via HMI or hard-wired selector before triggering Cmd_EStop.
CAT0 — Uncontrolled Stop (Immediate)
Cmd_EStop = TRUE, StopCategory = 0
│
└──▶ State → FAULTED
ALL outputs := FALSE (same PLC scan)
FaultCode := 11
- Power removed from actuators immediately — no "safe" motion completes
- Required for: hazardous energy, fire risk, collision imminent
- Hardware: typically wired directly to safety relay, not via PLC
CAT1 — Controlled Stop
Cmd_EStop = TRUE, StopCategory = 1
│
└──▶ State → STOPPING_CAT1
Current step continues executing (sensor/timer logic active)
CAT1 guard timer starts (10 s)
│
├── Step advance condition met ──▶ State → STOPPED (clean stop)
│
└── Timer.Q (timeout) ──▶ State → FAULTED, FaultCode = 20
- Allows servo drives, cylinders, and the weld head to complete their safe end-position before power is removed
- Prevents mechanical damage from mid-stroke stops
- 10 s
CAT1_TIMEOUTconstant protects against hangs — adjust for your application
CAT2 — Controlled Stop (Power Maintained)
Cmd_EStop = TRUE, StopCategory = 2 (or Cmd_Stop rising edge)
│
└──▶ State → STOPPED
Outputs frozen at current values
Drives/brakes remain energised (position maintained)
Cmd_Reset required to return to IDLE
- Used for: planned end-of-shift, material change, inspection
- Unlike PAUSE, requires explicit Reset rather than Start to resume
7. Pause vs Stop
PAUSE (Cmd_Pause) |
STOP (Cmd_Stop) |
|
|---|---|---|
| Activation | Rising edge Cmd_Pause |
Rising edge Cmd_Stop |
| IEC Category | — (not a stop category) | CAT2 |
| Outputs | Held at current state | Held at current state |
| Resume | Cmd_Start → continues same step |
Cmd_Reset → returns to IDLE |
| Typical use | Short interruption (fork truck, material feed) | Planned stop, shift change, part change |
| From safety fault? | Cannot resume if door open | Cannot reset if E-Stop active |
| Step continuity | Resumes mid-step (timer paused) | Restarts from Step 1 after reset |
Important: In PAUSED state, step timers stop counting (their
INbit goes FALSE because_state ≠ STATE_RUNNING). When resumed, timers restart from zero for the current step. If this is undesirable for your application (e.g. partial gas purge time), modify the timerINcondition to also includeSTATE_PAUSED.
8. Step-by-Step Breakdown
Step 1 — Home Position Verify 🔒 Safety-Locked
Sensors : Sen_HomeFwd (at home) + Sen_HomeBwd (NOT in work zone)
Actuators: NONE
Advance : Sen_HomeFwd = TRUE AND Sen_HomeBwd = FALSE
Lock : Safety-locked — SkipStep ignored
Purpose : Confirm fixture/robot is at safe starting co-ordinate before
clamping a part. Two-sensor logic eliminates single-sensor failure.
Step 2 — Clamp Workpiece
Sensors : Sen_ClampClosed (1 sensor)
Actuators: Act_Clamp ON
Advance : Sen_ClampClosed = TRUE
Purpose : Engage pneumatic clamp jaw on the workpiece.
Act_Clamp remains energised throughout steps 2–9.
Step 3 — Extend Weld Head
Sensors : Sen_HeadAtWeldPos (FWD) + Sen_HeadRetracted (BWD — conflict check)
Actuators: Act_HeadExtend ON
Advance : Sen_HeadAtWeldPos = TRUE (FWD sensor)
Purpose : Drive weld torch to the weld start position.
FWD+BWD conflict detection → FaultCode 30 if both TRUE.
Step 4 — Pre-Purge Gas ⏱ Timer
Sensors : NONE
Actuators: Act_GasValve ON
Advance : Timer T#2S elapsed
Purpose : Flow shielding gas (Argon/CO₂ mix) before arc strike to
displace atmospheric oxygen from the weld zone.
Step 5 — Arc Strike 🔒 Safety-Locked
Sensors : Sen_ArcDetect (1 sensor)
Actuators: Act_WeldEnable ON + Act_GasValve ON
Advance : Sen_ArcDetect = TRUE
Lock : Safety-locked — arc MUST be confirmed before weld travel begins
Purpose : Enable the welder and wait for arc current feedback.
Without this lock, a failed arc strike could lead to cold welds.
Step 6 — Weld Travel ⏱ Timer
Sensors : NONE
Actuators: Act_WeldEnable ON + Act_GasValve ON
Advance : Timer T#4S elapsed
Purpose : Robot/axis traverses the weld seam. PLC holds weld outputs
stable for the defined weld duration. In real systems, replace
timer with a robot "weld complete" handshake DI.
Step 7 — Arc Off / Weld End 🔒 Safety-Locked
Sensors : Sen_ArcOff (1 sensor)
Actuators: Act_WeldEnable OFF (commanded off this step)
Act_GasValve ON (gas continues for pool protection)
Advance : Sen_ArcOff = TRUE
Lock : Safety-locked — arc extinction MUST be confirmed before motion
Purpose : Confirm the arc is truly off before allowing any mechanical
movement. Prevents weld spatter damage to optics/sensors.
Step 8 — Post-Purge Gas ⏱ Timer
Sensors : NONE
Actuators: Act_GasValve ON
Advance : Timer T#2.5S elapsed
Purpose : Continue shielding gas flow after arc off to protect the
cooling weld pool from oxidation.
Step 9 — Retract Weld Head
Sensors : Sen_HeadRetracted (BWD) + Sen_HeadAtWeldPos (FWD — conflict check)
Actuators: Act_HeadRetract ON, Act_HeadExtend OFF
Advance : Sen_HeadRetracted = TRUE AND Sen_HeadAtWeldPos = FALSE (BWD sensor)
Purpose : Return weld torch to safe retracted home position before
unclamp/eject. Uses the same sensor pair as Step 3.
Step 10 — Unclamp / Part Eject
Sensors : Sen_UnclampConf (1 sensor)
Actuators: Act_Clamp OFF, Act_Unclamp ON, Act_PartEject ON
Advance : Sen_UnclampConf = TRUE → COMPLETE
Purpose : Release the finished weld assembly and fire the ejector
cylinder to clear the fixture for the next part.
On advance, state → COMPLETE, CycleCount increments.
9. Step Advance Types
Three advance methods are used across the 10 steps:
Type A — Dual-Sensor (FWD + BWD)
Used by: Steps 1, 3, 9
// Step 3 example
_stepAdvReady := Sen_HeadAtWeldPos; // FWD sensor = advance condition
// Sen_HeadRetracted monitored separately for conflict detection
The two sensors serve different purposes:
- FWD sensor → advance trigger (target position reached)
- BWD sensor → interlock / conflict check (should be opposite state)
- Both TRUE simultaneously → FaultCode 30 (wiring fault or sensor failure)
Type B — Single Sensor
Used by: Steps 2, 5, 7, 10
// Step 2 example
_stepAdvReady := Sen_ClampClosed;
Simplest form. Step activates its actuator(s) and waits for confirmation feedback.
Type C — Timer Only (no sensor)
Used by: Steps 4, 6, 8
// Step 4 example — timer resets automatically when step changes
_stepTimer[4](IN := (_activeStep = 4 AND _state = STATE_RUNNING),
PT := T#2S);
_stepAdvReady := _stepTimer[4].Q;
The timer IN is gated on (_activeStep = N AND STATE_RUNNING). When the step changes, IN goes FALSE and the TON resets automatically — no manual reset logic required.
10. Skip / Disable / Safety-Lock
Disable a Step (permanent skip every cycle)
Set in the instance DB or via HMI write to _stepEnabled[N]:
// Example: disable step 6 (weld travel) for a tack-weld-only mode
"DB_WeldSeq"._stepEnabled[6] := FALSE;
Disabled steps are silently skipped by the WHILE loop that finds the next enabled step. The step's actuator outputs are never energised.
Skip Current Step (operator, one-time)
Rising edge on Cmd_SkipStep. The FB checks _stepSafetyLocked[_activeStep]:
Cmd_SkipStep (↑) ──→ Is step safety-locked?
YES → Ignore (no action, no feedback)
NO → _forceAdvance := TRUE → step advances next scan
Safety-Locked Steps
Set during initialisation:
_stepSafetyLocked[1] := TRUE; // Home verify
_stepSafetyLocked[5] := TRUE; // Arc strike
_stepSafetyLocked[7] := TRUE; // Arc off
Why lock these steps?
| Step | Risk if skipped |
|---|---|
| 1 — Home Verify | Clamp closes on robot arm / fixture not in position |
| 5 — Arc Strike | Weld travel with no arc = cold weld, undetected failure |
| 7 — Arc Off | Moving head while arc still live = flash, fire, damage |
To add safety-locking to other steps, set _stepSafetyLocked[N] := TRUE in the IF NOT _initDone block.
11. Fault Codes
| Code | Name | Cause | Resolution |
|---|---|---|---|
| 0 | No fault | Normal | — |
| 10 | Safety door open | Door opened during RUN or PAUSED | Close door → Cmd_Reset |
| 11 | E-Stop activated | Cmd_EStop = TRUE or Safety_EStopOK = FALSE |
Clear E-Stop → Cmd_Reset |
| 20 | CAT1 timeout | Step did not complete within CAT1_TIMEOUT (10 s) |
Investigate stuck actuator → Cmd_Reset |
| 30 | Sensor conflict | Sen_HeadAtWeldPos AND Sen_HeadRetracted both TRUE |
Check sensor wiring/target → Cmd_Reset |
| 40 | Step watchdog | Step active for > WATCHDOG_TIME (30 s) |
Investigate jammed actuator or missing sensor → Cmd_Reset |
12. HMI Integration
Recommended HMI Tags
| HMI Tag | PLC Address | Notes |
|---|---|---|
SeqState |
%MW22 |
Use value display + state text list |
ActiveStep |
%MW20 |
Highlight active step on step diagram |
FaultCode |
%MW24 |
Alarm trigger with code text list |
CycleCount |
%MD30 |
Production counter display |
StepAdvanceReady |
%M5.0 |
Green indicator on each step |
IncrWaiting |
%M5.1 |
Flashing "Press INCR" indicator |
StopCategory |
%MW10 |
Selector: 0 / 1 / 2 |
State Text List (for SeqState display)
0 = "IDLE — Ready"
1 = "RUNNING"
2 = "PAUSED"
3 = "STOPPING (CAT1)"
4 = "STOPPED"
5 = "FAULTED"
6 = "CYCLE COMPLETE"
Fault Code Alarm List
10 = "Safety door opened — close door and reset"
11 = "E-Stop activated — clear E-Stop and reset"
20 = "CAT1 stop timeout — check step actuator"
30 = "Head sensor conflict — check I0.3 and I0.4"
40 = "Step watchdog timeout — step did not complete in 30 s"
13. TIA Portal Setup
Creating the Instance DB
- In the project tree, right-click the program folder → Add new block
- Select Data Block → name it
DB_WeldSeq - Set the block type to Instance DB of
FB_WeldSequencer - Compile
Calling the FB
Add to your cyclic interrupt OB (e.g. OB30 at 10 ms) or OB1:
"DB_WeldSeq"(
Mode_Auto := "HMI_ModeAuto",
Mode_Incr := "HMI_ModeIncr",
Cmd_Start := "PB_Start",
Cmd_Pause := "PB_Pause",
Cmd_Stop := "PB_Stop",
Cmd_EStop := "SafetyRelay_EStop",
Cmd_Reset := "PB_Reset",
Cmd_Incr := "PB_Incr",
Cmd_SkipStep := "PB_SkipStep",
StopCategory := "HMI_StopCategory",
Safety_DoorClosed := "SafetyGate_Closed",
Safety_EStopOK := "SafetyRelay_OK",
Sen_HomeFwd := %I0.0,
Sen_HomeBwd := %I0.1,
Sen_ClampClosed := %I0.2,
Sen_HeadAtWeldPos := %I0.3,
Sen_HeadRetracted := %I0.4,
Sen_ArcDetect := %I0.5,
Sen_ArcOff := %I0.6,
Sen_UnclampConf := %I0.7,
Act_Clamp => %Q0.0,
Act_HeadExtend => %Q0.1,
Act_HeadRetract => %Q0.2,
Act_GasValve => %Q0.3,
Act_WeldEnable => %Q0.4,
Act_Unclamp => %Q0.5,
Act_PartEject => %Q0.6,
Seq_Running => %Q1.0,
Seq_Paused => %Q1.1,
Seq_Faulted => %Q1.2,
Seq_Complete => %Q1.3,
ActiveStep => %MW20,
SeqState => %MW22,
FaultCode => %MW24,
StepAdvanceReady => %M5.0,
IncrWaiting => %M5.1,
CycleCount => %MD30
);
Adjusting Step Configuration at Runtime
Write to the instance DB directly (e.g. from HMI or during commissioning):
// Disable step 6 (bypass weld travel for testing)
"DB_WeldSeq"._stepEnabled[6] := FALSE;
// Change pre-purge time to 3 seconds
"DB_WeldSeq"._stepTimerPreset[4] := T#3S;
// Enable step 6 again
"DB_WeldSeq"._stepEnabled[6] := TRUE;
Note: Timer preset changes take effect on the NEXT activation of that step (TON picks up the new
PTvalue when it starts).
14. Adapting the Code
Adding More Steps
- Change array bounds:
Array[1..N]in all 6 array declarations - Update
LAST_STEPconstant - Add a new
CASEbranch for each new step - Call additional step timers and watchdog timers explicitly
Replacing Timer Advance with Robot Handshake
Step 6 uses a timer for weld travel. In a real system with a robot controller:
// Replace timer advance in Step 6 with robot "weld complete" signal
6:
Act_WeldEnable := TRUE;
Act_GasValve := TRUE;
_stepAdvReady := Robot_WeldComplete; // Add this DI to VAR_INPUT
Adding More Sensor Types
For a step needing analog threshold advance (e.g. temperature):
// In step logic:
_stepAdvReady := (TempSensor_mV > 4500); // Weld pool temp threshold
Multiple Sequencer Instances
Create multiple instance DBs for parallel lines:
"DB_WeldSeq_Line1"(...);
"DB_WeldSeq_Line2"(...);
Each instance is completely independent with its own state, timers, and counter.
Changing CAT1 Timeout
// In VAR CONSTANT section:
CAT1_TIMEOUT : Time := T#15S; // Increase for slower machinery
Or make it configurable via VAR_INPUT if different cells need different values.
15. Safety Notes
⚠️ This code is a demonstration template. It does NOT constitute a validated safety function and must NOT be used as-is for CE-marked or safety-certified applications without a proper risk assessment and SISTEMA analysis.
Minimum Requirements Before Deployment
- Full HAZOP / risk assessment per ISO 12100
- E-Stop circuit designed to ISO 13850 — hardware safety relay, not PLC output
- Safety door interlocks to ISO 14119 — use safety-rated sensors
- Emergency stop category confirmed per IEC 60204-1 Section 9.2
- CAT1 stop implementation validated: actuators must de-energise AFTER safe position confirmed
- Dual-channel safety inputs for CAT3/PLd or higher
- Functional safety assessment if PL ≥ c required (consider SIMATIC S7-1500F / F-FB)
- Factory Acceptance Test (FAT) covering all modes, stop categories, and fault scenarios
Software Safety Good Practice (Applied in This Code)
- All output variables cleared to
FALSEat the top of every scan before step logic re-energises them — eliminates "stuck on" from removed steps - FAULTED state drives all outputs to FALSE (Section 6 override)
- E-Stop and door monitoring execute BEFORE the state machine — highest priority
- Safety-locked steps enforce physical interlocks in software as a secondary barrier
- Sensor conflict detection for dual-sensor pairs
- Per-step watchdog timers catch hung steps before operators notice
Changelog
| Version | Date | Notes |
|---|---|---|
| 0.1 | 2025 | Initial release — 10-step welding cell demo |
License
MIT License — free to use and adapt for commercial or personal projects. Attribution appreciated but not required.
Generated for S7-1500 / TIA Portal V18+. Tested syntax against SCL compiler rules. Always perform a full offline simulation before deploying to hardware.