FUNCTION "FC_LowPassFilter" : Void
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.1
VAR_INPUT
analog_input : Real; // Raw analog input signal
alpha : Real := 0.8; // Smoothing factor (0.0 to 1.0)
enable : Bool := TRUE; // Enable filter
reset : Bool := FALSE; // Reset filter output to current input
END_VAR
VAR_OUTPUT
low_passed_output : Real; // Filtered output signal
END_VAR
VAR_IN_OUT
END_VAR
VAR
prev_output : Real; // Previous filtered output (retains value)
prev_input : Real; // Previous raw input
initialized : Bool := FALSE; // First-run flag
END_VAR
VAR_TEMP
END_VAR
BEGIN
// Clamp alpha to valid range [0.0, 1.0]
IF #alpha < 0.0 THEN
#alpha := 0.0;
ELSIF #alpha > 1.0 THEN
#alpha := 1.0;
END_IF;
// Handle reset
IF #reset THEN
#low_passed_output := #analog_input;
#prev_output := #analog_input;
#prev_input := #analog_input;
#initialized := TRUE;
RETURN;
END_IF;
// Skip if disabled
IF NOT #enable THEN
#low_passed_output := #analog_input;
RETURN;
END_IF;
// Initialize on first run to prevent startup transient
IF NOT #initialized THEN
#low_passed_output := #analog_input;
#prev_output := #analog_input;
#prev_input := #analog_input;
#initialized := TRUE;
RETURN;
END_IF;
// First-order IIR low-pass filter: Y(k) = alpha * Y(k-1) + (1 - alpha) * X(k-1)
#low_passed_output := (#alpha * #prev_output) + ((1.0 - #alpha) * #prev_input);
// Update previous values for next cycle
#prev_output := #low_passed_output;
#prev_input := #analog_input;
END_FUNCTION
Usage Example (in another block)
scl
// Call the filter with alpha = 0.9 (heavy smoothing)
"FC_LowPassFilter"(
analog_input := "Raw_Pressure_Sensor",
alpha := 0.9,
enable := TRUE,
reset := "Sensor_Fault",
low_passed_output => "Filtered_Pressure"
);
Tuning Guidelines
Tuning Guidelines
| Alpha | Behavior | Use Case |
|---|---|---|
| 0.95 – 0.99 | Very heavy smoothing, slow response | Very noisy signals, slow processes |
| 0.80 – 0.90 | Moderate smoothing | General purpose (default 0.8) |
| 0.50 – 0.70 | Light smoothing, responsive | Faster processes, moderate noise |
| 0.10 – 0.40 | Minimal smoothing, very responsive | Clean signals needing slight damping |
Tip: For a given cutoff frequency
f_cand sample timeT_s, you can calculate alpha as:\alpha = e^{-2\pi \cdot f_c \cdot T_s}